RIS citation export for WE3AO05: Helium Mass Flow System Integrated into EPICS for Online SRF Cavity Q Measurements

TY  - CONF
AU  - Jordan, K.
AU  - Biallas, G.H.
AU  - Christian, D.P.
AU  - Croke, G.R.
AU  - Jayne, J.P.
AU  - Tiefenback, M.G.
AU  - Wilson, C.M.
ED  - Schaa, Volker RW
ED  - Götz, Andy
ED  - Venter, Johan
ED  - White, Karen
ED  - Robichon, Marie
ED  - Rowland, Vivienne
TI  - Helium Mass Flow System Integrated into EPICS for Online SRF Cavity Q Measurements
J2  - Proc. of ICALEPCS2023, Cape Town, South Africa, 09-13 October 2023
CY  - Cape Town, South Africa
T2  - International Conference on Accelerator and Large Experimental Physics Control Systems
T3  - 19
LA  - english
AB  - The SBIR funded Helium Mass Flow Monitor System, developed by Jefferson Lab and Hyperboloid LLC, is designed to measure the health of cavities in a Cryomodule in real-time. It addresses the problem of cavities with low Q₀, which generate excess heat and evaporation from the 2 K super-fluid helium bath used to cool the cavities. The system utilizes a unique meter that is based on a superconducting component. This device enables high-resolution measurements of the power dissipated in the cryomodule while the accelerator is operating. It can also measure individual Cavity Q₀s when the beam is turned off. The Linux-based control system is an integral part of this device, providing the necessary control and data processing capabilities. The initial implementation of the Helium Mass Flow Monitor System at Jefferson Lab was done using LabView, a couple of current sources & a nano-voltmeter. Once the device was proven to work at 2K the controls transitioned to a hand wired PCB & Raspberry Pi interfaced to the open-source Experimental Physics and Industrial Control System (EPICS) control system. The EE support group preferred to support a LabJack T7 over the rPi. 12 chassis were built and the system is being deployed as the cryogenic U-Tubes become available.
PB  - JACoW Publishing
CP  - Geneva, Switzerland
SP  - 1071
EP  - 1076
KW  - cryomodule
KW  - cavity
KW  - controls
KW  - operation
KW  - interface
DA  - 2024/02
PY  - 2024
SN  - 2226-0358